Nu-Gen Online Three Phase UPS is a Double Conversion UPS with Output PF@0.9 to cater large systems within Compact design.Its designed with Microprocessor to ensure Constant Voltage and Constant Frequency even at very poor power contions and fluctuations sites.
Nu-Gen Online UPS Systems are very much suitable for Medical Equipments/CNC Machines/Large Industries/IT/ITES/BIO Equipments etc
Model Capacity |
|
||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Input: | |||||||||||||
Rated AC Voltage | 380V / 400V / 415V AC (3Ph+N+PE) | ||||||||||||
Voltage Range | 290V ~ 480V AC ± 5V | ||||||||||||
Frequency Range | 50 / 60 Hz ± 10% Auto Sensing | ||||||||||||
Power Factor | 0.99 | ||||||||||||
Walk-in Time | 5 ~ 300 Sec. (Configurable) | ||||||||||||
ByPass | |||||||||||||
Rated Voltage | 380V / 400V / 415V AC (3Ph+N+PE) | ||||||||||||
Voltage Range | + 20%, -30% (Configurable) | ||||||||||||
Frequency Range | 50 / 60 Hz ± 10% (Configurable) | ||||||||||||
Battery | |||||||||||||
Battery Voltage | 384V DC Standard (348 ~ 384 Configurable) | ||||||||||||
Ripple | 1% | ||||||||||||
Charging Current Max. | (A) 0.10C to 0.25C upto 100~300Ah at 100% Load (Configurable) | ||||||||||||
Output | |||||||||||||
Rated Voltage | 380V / 400V / 415V AC (3Ph+N) | ||||||||||||
Frequency Range | Auto Sensing 50 / 60 Hz ± 1~10% Sync Mode (Configurable), 50/60 Hz ± 0.1 Hz Battery Mode | ||||||||||||
Voltage Regulation | ±1% | ||||||||||||
Harmonic Distortion (THDv) | 1% Linear Load, 5% Non-Linear Load | ||||||||||||
Crest Factor / Transfer Time | 3:1 / Zero | ||||||||||||
Efficiency | Up to 95% Dual Conversion Mode, 99% ECO Mode | ||||||||||||
Overload | 125% for 10 Min, 150% for 1 Min, 150% for 300 ms | ||||||||||||
System Features | |||||||||||||
Parallel | Up to 6 Units (Optional) | ||||||||||||
Display | LCD + LED | ||||||||||||
IP Rating | IP 20 | ||||||||||||
Alarm / Protection | Short Circuit, Input Under/Over Voltage, Over Temperature, Over Current, Over Load, DC BUS Under / Over Voltage and Battery low | ||||||||||||
Audible Alarms | Alarm for batt. Low, DC High, Inverter Under/Over Voltage, Overload, Short Circuit, Fan Failure & UPS Fault | ||||||||||||
LED Indicatios | Bypass, Mains, Battery and Fault | ||||||||||||
Input Voltage & Freq.; Output Voltage, Current, KVA, KW, Total Power, PF, Load % Per Phase, Load % Total & Freq.; Bypass Voltage & Freq.; Inverter Voltage & Freq.; Battery Voltage | |||||||||||||
LCD Display Information | DC Bus Voltage, Charging Current, Discharging Current, Temperature. | ||||||||||||
Environmental | |||||||||||||
Temperature Operating: | 0~45°C, Storage: -10ºC ~ 55ºC | ||||||||||||
Humidity / Altitude | 0~95% RH Non-condersing / <1500 M | ||||||||||||
Noise | Low Audible Noise Level | ||||||||||||
Standards | |||||||||||||
Quality | ISO 9000, ISO 14001, OHSAS 18001, ISO 27001, RoHS | ||||||||||||
Safety | IEC/EN62040-1 | ||||||||||||
EMC / Performance | IEC/EN62040-2; IEC/EN62040-3, Complying to CE | ||||||||||||
Physical | |||||||||||||
Dimensions WxDxH (mm) | 405x656x817 404x656x941 432x821x1159 | ||||||||||||
Weight (Kg) | 118 120 145 198 278 365 | ||||||||||||
COMMUNICATION INTERFACE | |||||||||||||
Standard | RS-232 / Dry Contact / RS-485 | ||||||||||||
Optional | SNMP / ModBus / USB | ||||||||||||
Monitoring Software | NetAgent / Muser4000 |